InteliLite Global Guide
664
Related applications AMF, MRS
Description
This alarm occurs if the gen-set shall be stopped, but some symptom indicates that
it is not stopped. The period when the gen-set shall be stopped begins after the
FUEL SOLENOID (PAGE 572) has been switched off and time delay Stop Time
(page 203) has elapsed and lasts for the entire time the FUEL SOLENOID (PAGE
572) or STARTER (PAGE 597) are off.
Image 9.13 Stop Fail
Note: Gen-set cannot be started until this alarm is inactive and reset.
6 back to List of alarms level 1
Other type
Alarm Type Alarm indication
Alarmlist message After-Treatment
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when appropriate after-treatment lamp is active.
After-Treatment
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Dual Operation Different FW Version
Alarm evaluated Only during dual operation
Related applications AMF, MRS
Description
This alarm is active when FW version (all numbers are checked) or Branch of
Master and Slave is different.
Dual Operation Different FW Version
6 back to List of alarms level 1

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals