InteliLite Global Guide
677
Alarm Type Shutdown
Alarmlist message Sd Generator L1L2 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 1 and
2. The following setpoints are related to it:
Generator Overvoltage Sd (page 230)
Generator <> Voltage Delay (page 232)
Sd Generator L1L2 > Voltage
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator L1L2 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 1 and
2. The following setpoints are related to it:
Generator Undervoltage BOC (page 231)
Generator <> Voltage Delay (page 232)
Sd Generator L1L2 < Voltage
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator L2 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 2. The following
setpoints are related to it:
Generator Overvoltage Sd (page 230)
Generator <> Voltage Delay (page 232)
Sd Generator L2 > Voltage
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator L2 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phases 2. The following
setpoints are related to it:
Generator Undervoltage BOC (page 231)
Generator <> Voltage Delay (page 232)
Sd Generator L2 < Voltage