InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 123
IL-NT-AMF-2.2-Reference Guide.pdf
IL-NT-GPRS is switched off
IL-NT-GPRS is switched on
IL-NT-GPRS – error in initialization
IL-NT-GPRS – not possible to set the APN
IL-NT-GPRS – not possible to connect to GPRS network
IL-NT-GPRS – not possible to retrieve IP address
IL-NT-GPRS – not accepted DNS IP address
Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or unknown
status of SIM locking
Not possible to read the SIM card parameters
GSM modem did not accepted particular initialization command, possibly caused by
locked SIM card
Bad answer to complement initialization string
Not possible to read GSM signal strength
Unsuccessful registration to CDMA network
Controller couldn´t detect IL-NT GPRS module communication speed.
Only running communication is needed to indicate
AirGate Diag – Diagnostic Code for AirGate connection
Table of Diagnostic Codes:
Waiting for connection to AirGate Server
Controller registered, waiting for authorization
Not possible to register, controller blacklisted
Not possible to register, server has no more capacity
Not possible to register, other reason
Controller registered and authorized
SMS Commands
To control the gen-set equipped with InteliCompact
NT
controller and IL-NT GPRS communication
module (or modem) via SMS requests, send an SMS in the structure of:
# xxxx, yyyy, zzzz, etc.
to the telephone number of the SIM card in your IL-NT-GPRS module (or modem). Where the “#” mark
means the controller access code, “xxxx” means the Command 1, “yyyy” is Command 2, “zzzz” is
Command 3, etc.
Table of SMS requests:
Start the engine in MAN mode.
Stop the engine in MAN mode.
Acknowledging alarms and deactivating the horn output.
Closing GCB in MAN and TEST mode.
Opening GCB in MAN and TEST mode.
Closing MCB in MAN and TEST mode (only in IC-NT SPTM).
Opening MCB in MAN and TEST mode (only in IC-NT SPTM).