IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
116
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for start.
Setpoint: #%LdResStrt 4
Group
Pwr Management
Range [units]
0 .. %LdResStop 4 [%]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e. Pwr
mgmt mode = REL (%) if the reserve set #4 is active. Learn more about reserves
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
Setpoint: #%LdResStop 4
Group
Pwr Management
Range [units]
#%LdResStrt 4 .. 110 [%]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in relative mode. i.e. Pwr
mgmt mode = REL (%) if the reserve set #4 is active. Learn more about reserves
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for start.
Setpoint: #NextStrt Del
Group
Pwr Management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
This setpoint is used to adjust the delay of starting the next gen-set when the
actual load reserve drops below the adjusted reserve for start, but the group is still
not overloaded.