Number of rings prior to answering the modem connection from PC to controller.
NOTE:
Any change of this setpoint is applied first after next switching the controller or
modem off and on or after disconnecting the modem from the controller and
connecting it back.
Setpoint: ActCallAttempt
Group
Act. calls/SMS
Range [units]
1 .. 250 [-]
Related FW
3.0
Description
This setpoint is used to adjust the maximum number of consequent attempts to
perform an active data call. The next attempt is performed 120s after the previous
unsuccessful attempt.
Setpoint: Acall+SMS lang
Group
Act. calls/SMS
Range [units]
1 .. 7 [-]
Related FW
3.0
Description
The setpoint specifies in which language the active SMS and e-mail messages
are issued. Adjust the setpoint to the index of the required language. The index
can be obtained from the tab Languages in GenConfig. Index 1 is always english.
Group: Date/Time
Setpoint: Time stamp act
Group
Date/Time
Range [units]
DISABLED, ENGINE RUNNING, ALWAYS [-]
Related FW
3.0
Description
The setpoint selects the Time stamp function mode.
DISABLED
The function is disabled.
ENGINE RUNNING
While the engine is running the Time stamps records
are recorded into the history log with period adjusted
by setpoint Time Stamp Per.
ALWAYS
The Time stamps records are recorded into the history
log with period adjusted by setpoint Time Stamp Per
all the time while the controler is switched on.