Generator current in phase L3.
NOTE:
The ratio between the current measured at the input terminals and the displayed
current is adjusted by the setpoints CT ratio prim and CT ratio sec.
Bank voltage unbalance. The value is calculated as maximal difference of two
phase voltages at one moment and expressed in % of the nominal voltage.
NOTE:
This value can be used for creating the generator voltage unbalance protection
using the "universal analog protections".
Bank current unbalance. The value is calculated as maximal difference of two
phase currents at one moment and expressed in % of the nominal current.
NOTE:
This value can be used for creating the generator current unbalance protection
using the "universal analog protections".
Differential frequency between the bank and the mains/bus.