IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
162
Related FW
3.0
Description
Actual relative reserve.
Value: Res rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual relative reserve for start. This value contains a copy of the setpoint
#%LdResStrt from the currently selected reserve set.
Value: ResStp rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual relative reserve - when the relative reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following:
[Nominal power of gen-set which is next to be stopped + ((%LdResStp/100) * Sum
of nominal powers of gen-sets loaded in power management except the one
which is next to be stopped)]/(Sum of nominal powers of gen-sets loaded in power
management).
#%LdResStop is used from the currently selected reserve set.
Value: MinR PWR
Group
Power management
Units
kW
Related FW
3.0
Description
Currently active Minimal Running Power level. If the value contains 0 the minimal
running power function is disabled.
Group: Sync/Load ctrl
Value: ActPwrReq
Group
Sync/Load ctrl
Units
kW
Related FW
3.0
Description
This value contains actual required load level, which is used as the input into the
load regulation loop in the parallel to mains operation.