IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
56
DISABLED
Pressing of the fault reset button (at any terminal or external button) resets
only inactive alarms. Active alarms remain in the alarmlist unchanged and must be reset
again when they become inactive.
ENABLED
Pressing of the fault reset button (at any terminal or external button) resets all alarms that
are currently present in the alarm list. Inactive alarms disappear from the alarm list
immediately, active alarms are changed to "confirmed" state and disappear when the
alarm condition disappear or the alarm starts to be blocked.
NOTE:
ENABLED position corresponds to the method how the IG-classic and IS-classic controllers handled the
alarms.