IS-NT-Async-SPI, SW Version 1.2, ©ComAp – February 2011
IS-NT-Async-SPI-1.2.PDF
67
Maximum positive deviation of one cylinder temperature from the average at the PminCylDifEval load. Alarm
can be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all
the time or after some time after start (depends on RunOnlyBlkDelX time).
Step: 1 °C
Range: ± 32000 °C
Max-CylDifPmin [ °C ]
Max-CylDifPmin = Maximum negative Cylinder temperature Difference at minimal gen-set Power level.
Maximum negative deviation of one cylinder temperature from the average at the PminCylDifEval. load.
Alarm can be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs)
– all the time or after some time after start (depends on RunOnlyBlkDelX time).
Step: 1 °C
Range: ± 32000 °C
Max+CylDifPnom [ °C ]
Max-CylDifPnom = Maximum positive Cylinder temperature Difference at nominal gen-set Power level.
Maximum positive deviation of one cylinder temperature from the average at the Nomin power. Alarm can be
activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all the time
or after some time after start (depends on RunOnlyBlkDelX time).
Step: 1 °C
Range: ± 32000 °C
Max-CylDifPnom [ °C ]
Max-CylDifPnom = Maximum negative Cylinder temperature Difference at nominal gen-set Power level.
Maximum negative deviation of one cylinder temperature from the average at the Nomin power. Alarm can
be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all the
time or after some time after start (depends on RunOnlyBlkDelX time).
Step: 1 °C
Range: ± 32000 °C
PminCylDifEval [ kW – MW* ]
Minimum gen-set Power for Cylinder temperature Difference evaluation. The protection is not evaluated, if
the gen-set power is lower than this limit.
Step: 0,1 kW / 1 kW / 0,01 MW*
Range: 0,0 kW – Nominal power*
*Note:
The actual setpoint units and range depend on setting of the Power format (see GenConfig manual).
CylDifEvalDel [ s ]
Cylinder temperature Difference Evaluation Delay.
Step: 1s
Range: 0 – 600 s
Cylinder temperature deviation protection type: warning