MainsPro G99TT 1.0.0 Global Guide
54
6 back to Appendix
12.1.1 Group: Basic
Uin
Selection of the measurement range to adjust the HW for maximum accuracy.
230 V the unit measures 230 VAC phase-neutral with max over-range 130% (300 VAC)
400 V the unit measures 400 V phase-phase with max over-range 130% (520 VAC)
120 V
the unit measures 120 VAC phase-neutral or on the secondary winding of the VT with
max over-range 130% (156 VAC)
Defaultsetting 230 V
6 back to Library of Setpoints
System
Selection of single phase or three-phase application. In case of single phase setting, the voltage on last two
phases and voltage asymmetry are not measured.
3ph the unit measures 3-phase system
1ph the unit measures single-phase system
Default setting 3ph
6 back to Library of Setpoints
DispT [min]
Setting of display backlight timeout since the last button activity.
Range 1..60 min
0 min = OFF, display is set to permanent backlight
Default setting 0 min
6 back to Library of Setpoints
Auto FR
Enables or disables the functionality of the automatic fault reset by internal timer.
ENABLED the functionality is enabled
DISABLED the functionality is disabled
Default setting ENABLED
6 back to Library of Setpoints