EasyManua.ls Logo

ComAp MainsPro G99TT - Group: LOM, A.LOM; Rstf>,F>> [%F>]; VS Lim, A.VS Lim [°]; ROCOF, A.ROCOF [Hz;S]

ComAp MainsPro G99TT
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MainsPro G99TT 1.0.0 Global Guide
60
Rstf>,f>> [%f>]
Frequency level at which the protection activates again after a trip caused by overfrequency. The TRIP status
will be terminated.
Range 90.0 - 100.0 %f>
0 = OFF, the reset threshold is not activated
Default setting 100.0 %f>
6 back to Library of Setpoints
Rstf<,f<< [%f<]
Frequency level at which the protection activates again after a trip caused by underfrequency. The TRIP
status will be terminated.
Range 100.0 - 110.0 %f<
0 = OFF, the reset threshold is not activated
Default setting 100.0 %f<
6 back to Library of Setpoints
12.1.5 Group: LOM, A.LOM
VS lim, A.VS lim [°]
Threshold at which the Vector shift protection is activated.
Range 1..50°
0 = OFF, the Vector shift protection is not enabled
Default setting
6 back to Library of Setpoints
ROCOF, A.ROCOF [Hz/s]
Threshold at which the Rate of change of frequency (ROCOF) protection is activated.
Range 0.01..10.00 Hz/s
0 = OFF, the ROCOF protection is not enabled
Default setting 1
6 back to Library of Setpoints

Table of Contents

Related product manuals