MainsPro G99TT 1.0.0 Global Guide
57
12.1.2 Group: V <>, A.V <>
V>, V>>, V<, V<<, A.V>, A.V>>, A.V<, A.V<< [V]
Threshold of 1st and 2nd stage overvoltage, and 1st and 2nd stage undervoltage protection, respectively.
Range 1..999 V
0 = OFF, the appropriate stage of voltage protection is not enabled
Default setting
V> 262 V
V>> 273 V
V< 184 V
V<< 0 V
Note: Please note, that the indicated setting is adjusted for "Star" connection of the measured voltage, i.e.
ph-to-N voltage measurement. In case of using "Delta" connection, the appropriate change of the setpoints to
ph-ph voltage is necessary.
6 back to Library of Setpoints
V> del, V>> del, V< del, V<< del [s]
Delay of the appropriate stage of the voltage protection.
Range 0.00..600.00 s
Default setting
V> Del 1.00 s
V>> Del 0.50 s
V< Del 2.50 s
V<< Del 0.50 s
6 back to Library of Setpoints
Avg V> [V]
Limit for Floating 10 minutes average overvoltage (page 34) protection.
Range 0..34000 V
0 = OFF, the 10 minutes average overvoltage protection is not enabled
Default setting 0 (OFF)
6 back to Library of Setpoints