EasyManua.ls Logo

ComAp MainsPro - Library of Setpoints

ComAp MainsPro
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mains pro 1.6.1 Global Guide
51
12.1 Library of Setpoints
MainsPro provides the possibility of dual setting of the protection functions setpoints. This setting may be used
in case that the installation is running in exceptional conditions with different requirements for protections
setting. Some groups of setpoints have their alternative setpoints identified by the same name, but with latter
A.” at the beginning (e.g. V<>, A.V<> etc.). By activating the binary switch Alt settings, the unit is immediately
switched to the setting, done in the “A.xx group, see Library of Binary switches on page 61.
Uin 52
System 52
DispT [min] 52
Auto FR 52
Auto FR Del [s] 53
Start Trip 53
Imp Len [s] 53
Bak Trp Del [s] 53
Ext 54
F.R. 54
Alt 54
Disable 54
V>, V>>, V<, V<<, A.V>, A.V>>, A.V<, A.V<< [V] 55
V> del, V>> del, V< del, V<< del [s] 55
Avg V> [V] 55
RstV>,V>> [%V>] 56
RstV<,V<< [%V<] 56
V unb, A.V unb [V] 56
V< pos, A.V< pos [V] 56
V> neg, A.V> neg [V] 57
dU del, A.dU del [s] 57
f>, f>>, f<, f<<, A.f>, A.f>>, A.f<, A.f<< [Hz] 57
f> del, f>> del, f< del, f<< del, A.f> del, A.f>> del, A.f< del, A.f<< del [s] 57
Rstf>,f>> [%f>] 58
Rstf<,f<< [%f<] 58
VS lim, A.VS lim [°] 58
ROCOF, A.ROCOF [Hz/s] 58
ROCOF filt, A.ROCOF filt [-] 59
LOM Init Del, A. LOM Init Del [s] 59
LOM Trp Del, A.LOM Trp Del [s] 59
ROCOF Del/A.ROCOF Del [s] 59
f(RE1-5) 60
6 back to Appendix

Table of Contents

Other manuals for ComAp MainsPro

Related product manuals