Rstf>,f>> [%f>]
Frequency level at which the protection activates again after a trip caused by overfrequency. The TRIP status
will be terminated.
Range 90.0 - 100.0 %f>
0 = OFF, the reset threshold is not activated
Default setting 100.0 %f>
6 back to Library of Setpoints
Rstf<,f<< [%f<]
Frequency level at which the protection activates again after a trip caused by underfrequency. The TRIP status
will be terminated.
Range 100.0 - 110.0 %f<
0 = OFF, the reset threshold is not activated
Default setting 100.0 %f<
6 back to Library of Setpoints
12.1.5 Group: LOM, A.LOM
VS lim, A.VS lim [°]
Threshold at which the Vector shift protection is activated.
Range 1..50°
0 = OFF, the Vector shift protection is not enabled
Default setting 0°
6 back to Library of Setpoints
ROCOF, A.ROCOF [Hz/s]
Threshold at which the Rate of change of frequency (ROCOF) protection is activated.
Range 0.01..10.00 Hz/s
0 = OFF, the ROCOF protection is not enabled
Default setting 1