12.3.26 BakTrpImp
Backup trip impulse relay; closes immediately if any of the CommTrpPer (page 63) or CommTrpImp (page
63) is activated and CB Feedback doesn't deactivate within Bak Trp Del. The length of the impulse can be
adjusted in Imp Len [s] (page 53). Opening of the relay does not mean end of trip state. The trip is terminated in
fault free state after a successful fault reset. During trip status, the relay does not react on any new failure and
also, if the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function
is blocked.
6 back to Relay outputs
12.3.27 !BakTrpImp
Inverse backup trip impulse relay; opens immediately if any of the CommTrpPer (page 63) or CommTrpImp
(page 63) is activated and CB Feedback doesn't deactivate within Bak Trp Del. The length of the impulse can
be adjusted in Imp Len [s] (page 53). Closing of the relay does not mean end of trip state. The trip is terminated
in fault free state after a successful fault reset. During trip status, the relay does not react on any new failure and
also, if the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function
is blocked.
6 back to Relay outputs