These parameters are:
1. On- delay: Is a function (in seconds) that will delay the chamber start up after a power
outage, to avoid all equipment starting simultaneously. Factory default values are
random numbers between 00 to 59. This value can be edited to the user’s convenience.
CONVIRON recommends setting a time delay not lower than 10 to 20 seconds. However,
this may vary according to the number of Units installed.
2. Time / date: Allows the user to set the actual date and time according to the time zone
where the unit is being installed.
3. Setup: Allows the User to adjust the maximum number of discreet levels of light that are
present in the Unit.
Model Maximum Light Level
A1000IN 1
A1000AR 3
A1000PG 3
A1000TC 1
A350 3
4. Security: The user may enable this function which restricts the access to some of the
controller features, such as programming, scheduling, etc. The user can set passwords
for up to three users with different passwords. See the CMP6010 Operator’s Manual