ASCII I/F
CoolMasterNet PRM Rev 0.7
18
www.coolautomation.com
© 2017 CoolAutomation
· Line is a CooLinkNet HVAC Line number in range L1..L4. L* means "any line". In some cases to provide
backward compatibility Line can be omitted from the UID.
· Dot is a separator between Line and Indoor Number. If Line is omitted or has a L* form, dot must also be
omitted.
· Indoor Number is an Indoor Unit number in HVAC system. Indoor Number can be '*' that means "any"
Examples:
Indoor Unit 102 on line L1
Indoor Unit 003 on line L2
Set of Indoor Units 100 on all lines
Set of Indoor Units 1xx on line L3 (L3.100, L3.101, ... )
Similar to L*203 (for backward compatibility only)
UID_STRICT
In some cases only specific Indoor Unit should be referenced by UID. In this case it is required to use
UID_STRICT in format Ln.XYY where '*' usage is prohibited.
6.2
Commands Reference
Synopsis and description of the commands listed below have the following notation:
· Parameters or parameters group in angle brackets < > are mandatory.
· Parameters or parameters group in square brackets [ ] are optional and can be omitted.
· The curly braces ( ) are used to denote group inside braces
· The | character between parameters inside brackets means OR.
6.2.1 Configuration Commands
set
line
ifconfig
boot
sddp
knx
props
link
plug
hdl
simul
gpio
info
modbus
set
SYNOPSIS
set [<SETTING> <VALUE>]
set defaults
DESCRIPTION
Query or change CoolMasterNet setting(s). Without parameters set command will list all supported settings