ASCII I/F
CoolMasterNet PRM Rev 0.7
19
www.coolautomation.com
© 2017 CoolAutomation
and their values. To change setting use format with <SETTING> and <VALUE>. Some settings are read only
(RO) and can not be changed.
set defaults will load default values to all settings
CoolMasterNet Serial Number
CoolMasterNet Firmware Version
CoolMasterNet Application
RS232 Interface baud rate. Default: 9600
RS232 Interface echo control. 0 - disabled, 1 - enabled
Exit Code format. 0 - numeric, 1 - verbose
aserver TCP port. Default: 10102
Temperature scale Celsius or Fahrenheit
PowerUp melody. The value is printed as melody name,
to change the melody its number should be typed. set
melody will list supported melodies and their numbers.
Indoor Units visibility regarding props command. - props
visibility applies only to LCD, 1 props visibility applies to
LCD and status/control commands, 0 - props visibility
logic is inverted and it applies to LCD and status/control
commands
Allowed number of HVAC lines. Can be changed through
encoded activation string.
* - Bold values are defaults.
EXAMPLE
Disable echo
>set echo 0
OK
Change aserver TCP port
>set aserver port 12345
OK
Load defaults
>set defaults
OK
Apply props visibility to status/control commands
>set filter visi 1
OK, Boot Required!
Set RS232 Interface to 19200, 8 data bits, even parity, 1 stop bit
>set baud 19200 8E1
OK
Set temperature scale to Fahrenheit
>set deg f
OK
Set PowerUp melody to 3
>set melody 3
OK
line
SYNOPSIS
line
line <PROPERTY> <Ln> <VAL>