ASCII I/F
CoolMasterNet PRM Rev 0.7
43
www.coolautomation.com
© 2017 CoolAutomation
L1.300 -
L1.301 +
L1.302 -
L2.100 ?
L2.101 ?
L2.102 ?
L2.103 ?
OK
Unset main RC: Indoor Unit 206 on line L2
>main L2.206 0
OK
Set new main RC: Indoor Unit 201 on line L2
>main L2.201 1
OK
vam
SYNOPSIS
vam <UID_STRICT> <a|b|x|n|l|L|h|H|s|t|A|+|->
vam
vam <UID_STRICT>
DESCRIPTION
Control Ventilation Unit.
· vam <UID_STRICT> - get Ventilation Unit status.
· vam - get all Ventilation Units status.
Heat Exchange (HExc) Mode
Turn on ventilation unit*
Turn off ventilation unit*
ON/OFF control of the Ventilation Unit is performed with regular on and off commands.
There are, though, dual units, that consist of Air Condition Unit and Ventilation unit. In this case on and off
commands will control the Air Condition Unit, while vam <UID_STRICT> +/vam <UID_STRICT> - will
control the Ventilation Unit.
EXAMPLE
Set Heat Exchange mode on Ventilation Unit 101 on Line L1
>vam L1.101 x