17COOLIUS A10 / Y10
4.2 Counter reset (UNLOCK CODE required)
Change lter and vacuum pump oil before reseting maintenance!
NOTE: Use genuine spare parts or their equivalent only.
The use of replacement parts which are not of equivalent quality may damage the equipment!
Go to website www.coolius-ac.com or call the hotline +497940981888188 to retrieve the UNLOCK CODE for
maintenance counter reset.
1. Press START to continue.
2. Use the COOLIUS SELECT to enter the maintenance
UNLOCK CODE obtained from www.coolius-ac.com.
Whendone,conrmbySTART.
• If the UNLOCK CODE is wrong, repeat the step 2.
• If the UNLOCK CODE is right, go to step 3.
3. Press X (CANCEL)keytoconrm.
4. Press X (CANCEL)keytoconrm.
Maintenance reset successfully completed.
5 Calibration
1. Select SERVICE and type password: 311299
2. Turn COOLIUS SELECT to navigate between:
• “Refrigerant weight scale” (or simply “Weight scale”).
• “Pressure transducer”.
3. Press ENTERtoconrm.
Get UNLOCK CODE
register:
BB111111
www.coolius-ac.com
A*******
A
34567890 BCDEFGHIJK
Counter reset.
Confirm by “X”
min. ///
Counter reset.
Confirm again!
Select:
Refr. weight scale