19COOLIUS A10 / Y10
Set the sample weight value
8. Turn COOLIUS SELECT to set the weight value.
9. When done, press STARTtoconrm.
Calibration completed.
5.2 Pressure transducer
IMPORTANT: The quick coupler must be assembled on the service hoses and the gauges must
show 0 (zero) pressure!
1. Press STARTtoconrm.
2. The vacuum pump starts and perform a short vacuum
phase.
After a few seconds, the value (ADC Points) must be
lower than:
250 for pressure transducer O-10 (Metal body)
500 for pressure transducer OT-1 (Black plastic body)
3. When the vacuum pump stops and the display shows:
Remove the LP service connector (service coupler) from
the BLUE service hose, then press ENTERtoconrm.
Wait for screen change!
4. Turn COOLIUS SELECT to set the atmospheric pressu-
re (ex: 1010 mb).
When done, press STARTtoconrm.
5. Wait the end, then press STOP to exit.
Calibration completed.
Set the sample
weight value.
g.
Confirm by “START”
Wait!
xx
Remove the LP
connector from the
service hose.
Set the atmospheric
pressure value (abs)
mb. 0