Introduction
ServiceInformationS280-42-1 provides installation, oper-
ation, and service instructions for the Type NOVA
three-
phase, microprocessor-controlled recloser. Before install-
ing and operating this recloser, carefully read and under-
stand the contents of this manual.
Read This Manual First
Read and understand the contents of this manual and fol-
low all locally approved procedures and safety practices
before installing or operating this equipment. This recloser
is used in conjunction with a Cooper Power Systems
microprocessor-based recloser control.
If used with a Form 4C control, refer to Service
InformationS280-77-1.
If used with a Form 4D Pole Mount control, refer to
ServiceInformationS280-104-1.
If used with a Form 5 control, refer to Service
InformationS280-79-10.
If used with a Form 6 Rack Mount control, refer to
ServiceInformationS280-70-1.
If used with a Form 6 Yard Mount control, refer to
ServiceInformationS280-70-2.
If used with a Form 6 Pole Mount control, refer to
ServiceInformationS280-70-3.
If used with an FXB control, refer to ServiceInformation
S280-78-1.
The NOVA recloser with Type A mechanism/control-
powered interface is not compatible with the FXB
control.
The NOVA recloser is not compatible with the Form 2,
Form 3, nor Form 3A controls.
Additional Information
These instructions cannot cover all details or vari ations
in the equipment, procedures, or process described nor
provide directions for meeting every possible contin gency
during installation, operation, or maintenance. For addi-
tional information, contact your Cooper Power Systems
representative.
Acceptance and Initial Inspection
Each recloser is completely assembled, tested, and
inspected at the factory. It is in good condition when
accepted by the carrier for shipment. Upon receipt, inspect
the shipping container for signs of damage. Unpack the
recloser and inspect it thoroughly for damage incurred dur-
ing shipment. If damage is discovered, file a claim with the
carrier immediately.
Handling and Storage
Be careful during handling and storage of the recloser to
minimize the possibility of damage. Refer to the Moving
the Recloser and Lifting the Recloser sections. If the
recloser is to be stored for any length of time prior to instal-
lation, provide a clean, dry storage area.
Cooper Power Systems recommends transporting NOVA
reclosers in the closed position to maximize the operational
performance of the unit.
Standards
The Type NOVA reclosers are designed and tested in
accordance with:
IEEE Standard C37.60-2003
IEEE Standard C37.61-1973
ANSI C37.85 - 2002
Quality Standards
ISO 9001 Certified Quality Management System
Description of Operation
The Type NOVA recloser is a three-phase, vacuum-
interrupting recloser designed for electrical distribution
systems through 34.5 kV. The NOVA recloser is designed
and tested to be compatible with Cooper Power System
control types. The Type NOVA recloser is available with
two configuration options: control-powered interface and
auxiliary-powered interface.
The solid polymer insulation system does not rely on a gas-
eous, liquid, or foam dielectric. The NOVA recloser is highly
resistant to ozone, oxygen, moisture, contamination, and
ultraviolet light. The NOVA recloser has three solid-polymer
interrupter modules, an embedded current transformer,
and a standard aluminum mechanism housing. It is suit-
able for operation through a temperature range of -40°C
to +55°C.