Sensed Currents
Phase Current Individual Phase Currents:
Range: 1 A to 10,000 A for 500:1 CTs
2 A to 20,000 A for 1000:1 CTs
4 A to 40,000 A for 2000:1 CTs
Accuracy:± 1 mA from 10 mA to 125 mA
0.8% from 125 mA to 1600 mA
(Control only – does not include sensor
tolerance.)
Ground Current Vector Sum of Three-Phase
Currents:
Range: 1 A to 5,000 A for 500:1 CTs
2 A to 10,000 A for 1000:1 CTs
4 A to 20,000 A for 2000:1 CTs
Accuracy: ± 3 mA from 10 mA to 125 mA
2.4% from 125 mA to 1600 mA
(Control only – does not include sensor tol-
erance, but does include the phase current
summing process.)
Sensed Source Voltages
Three-phase voltages used in voltage, power and power-
factor related calculations:
Voltage measurement accuracy:
± 0.4V from 5 V to 80V
0.5% from 80 V to 135V
Kyle Form 5/Triple-Single Microprocessor-Based Recloser Control Installation and Operation Instructions
30
INPUT ACCURACY