Drying of floor structures
For drying of floor structures with easily dried insulation like glass wool or none insulated structures,
the CTR A ES is with advantage used with a high pressure fan like the HP2000 in accordance with the
schematic sketch below. Note that the capacity of the fan widely exceeds that of the dehumidifier
and therefore the fan must not be directly connected to the dehumidifier by hose as this would
seriously affect its function and degrade is efficiency. Instead, leave the dry air hose from the
dehumidifier on the floor just by the fan so that the dry air is sucked in along with ambient air.
Drying of floor structure. Note that the dry air hose of the dryer on the right is not
directly connected to the fan but left just next to its inlet.