EasyManua.ls Logo

COZY DVCF403C-H - Minimum Clearances

COZY DVCF403C-H
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1018028-A
Page 6
CLEARANCES - Continued
1. MINIMUM CLEARANCES
• Side Wall: Min. Clearance = 4”
(See Fig. 1) NOTE: The unit may be recessed and rest directly
against side studs and the inside surface of the rear wall.
• Ceiling: Min. Clearance = 4”
(See Fig. 1)
• Floor: Min. Clearance = 0”
(See Fig. 1)
•
FromtheSideoftheVentCaptoAnyProtruding
ObstructionsorCorners: Min. Clearance = 12”
(See Fig. 2b)
•
FromanyWindowtotheSideoftheVentCap
DVCF553C, 554C, 557C and 558C
FIG. 2-B
12”
Min.
12”
Min.
24” Minimum
12” Minimum
DVCF403C, 404C, 407C and 408C
FIG. 2-A
9”
Min.
12”
Min.
24” Minimum
12” Minimum
2. RESIDENTIAL GARAGE INSTALLATION:
Gas utilization equipment in residential garages shall be
installed so that all burners and burner ignition devices are
located not less than 18 inches (46 cm) above the oor. Such
equipment shall be located, or protected so it is not subject
to damage by a moving vehicle. Use care in selecting a good
location within the garage.
• DO NOT locate the appliance where heated air will
be directed onto a nearby parked vehicle.
Paint may discolor or rubber
may harden and crack.
• DO NOT allow heated discharge air to blow directly
onto open or closed containers of paint, gasoline or
other liquids having ammable vapors.
DVCF403,404,
407,&408C
DVCF553,554,
557&558C
Min. Clearance = 9”
(See Figure 2)
Min. Clearance = 12”
(See Figure 2b)
•
FromanyOverhangingProjectiontoTopofVentCap
Min. Clearance = 24”
(See Figure 2)
CEILING
4” Minimum
4” Minimum
SIDE
WALL
FLOOR 0”
FIG. 1