UHS5 Programming
For Dimming models including ‘-DD/SR and ‘-ADmodels
Number of shi
presses
Parameter
Name
Default
Value
0
SHIFT 1 SHIFT 2
1
SHIFT 1 SHIFT 2
2
SHIFT 1 SHIFT 2
3
SHIFT 1 SHIFT 2
UHS5 Handset
Graphics
Description
On/ Raise On Raise
Cancel
overide on
Turn lights on or to raise lights.
O/ Lower O Lower
Cancel
overide o
Turn lights o or to lower lights.
Walk test O On O
When set to On this causes a red LED
to ash on the sensor when it detects
movement. Use this feature to check for
adequate sensitivity levels.
Time Out
(Time
adjustment)
20 mins
1, 10 & 20
minutes
5, 15 & 30
minutes
10 seconds
(5/1 button)
Once the detector is turned on, this
value sets how long the lights will stay
on once movement has ceased.
LUX on level
(Switch level
on)
9 2, 5 & 7 4, 6 & 9
LUX level setting to prevent the
luminaires from being switched on if
the light level is sucient (adjustable
between 2 and 7). The luminaires will
always be switched on at level 9.
Light Level
6
9 (V3)
2, 5 & 7 4, 6 & 9
Sets a target preset light level between
2 and 7 to be maintained by the lighting
system. 9 = disabled.
LUX o level
(Switch level
o)
9 2, 5 & 7 4, 6 & 9
LUX level setting switches the luminaires
o if the light level goes above the
setting (adjustable between 2 and 7).
Level 9 will always keep the lights on.
This setting can be used for “window
row switching”.
Note: the LUX O Level value must always
be greater than the LUX On Level value.
Load type
DALI
D_ON (V3)
2 – Dali
7 – DSI
2 – D_ON
Sets the ballast control protocol to be
used by the output channel.
Sensitivity 9 1, 5 & 9 3, 6 & 8
For both ON and OFF, sensitivity level for
detecting movement.
1 = low sensitivity
9 = high sensitivity
Defaults D
Returns the unit to the default settings.
Burn-in
(Hours)
0 0 50 100
Determines how long the output will
be at 100% so that lamps ‘burn-in’. The
’burn-in’ time is not aected by power
supply interruptions.
Presence/
Absence
Presence Presence Absence
Presence mode allows the output to
turn on when movement is detected
and o when movement ceases.
Absence mode allows the output to turn
o when movement ceases, but must be
manually turned on rst.
Shi
Use this button to select the settings in
red and blue signied by the ‘Shi 1’ and
Shi 2’ LEDs
For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device.
Point the handset at the sensor and send the required programming commands to the unit as shown below. Valid commands
will be indicated by a red LED ash. See page 1 for details of other LED responses.
Note: other functions on the UHS5 which are not shown below are not applicable to this product.