UNLCDHS Programming – Output Ch. 2
Advance Parameters available for Dimming models including
-DD/SRand ‘-ADand their variants only
Parameter Default Range / Option Description
On Scene (V3) 1 1 – 8 Default scene to switch to aer the detector times out and then powers up.
Load Type
(Gear type)
0_10V
or D-ON
depending
on product
DSI / D-ON / 0_10V /
1_10V depending on
product
Indicates the dimming ballast type.
DSI
Sets the drivers control protocol to DSI for DD sensors.
D-ON
Sets the drivers control protocol to DALI for DD sensors.
1_10V
Sets the drivers control to 1-10V output for analogue dimming devices for AD sensors.
0_10V
Sets the drivers control to 0-10V output for analogue dimming devices for AD sensors.
DALI
Note: The DALI option may be found on the handset but this is replaced by the D-ON
option.
On Value 99 0 – 99 Dimmed output level when lights manually switched on or via detection of occupancy.
Fade On Level (V3) 99 0 – 99 For future use. Leave as default values.
Gradual Fade On
Time (V3)
0 0 – 99 minutes For future use. Leave as default values.
Fade O Level (V3) 0 0 – 99 Set the Stepped Fade O light output level (%) to hold aer occupancy has timed
out. This level which would last the period specied in the Stepped Fade O Time
parameter before turning o.
Note when this function is used, both channel 1 and channel 2 will work and switch
o together and can no longer be treated as independently controlled.
Gradual Fade O
Time (V3)
0 0 – 99 minutes For future use. Leave as default values.
Stepped Fade O
Time (V3)
0 0 – 99 minutes Sets the time period of the Stepped Fade output level before turning o.
Dim Output (V3) 0 0 – 99 Use with the Readback function to see the dimming output level currently being
sent to luminaires.
Fade Value (V2) 10 0 – 99 Aer occupancy ceases, this dimming output level is loaded for the fade time.
Fade Time (V2) 0 0 – 99 minutes This is the time period (adjustable between 0 and 99 minutes) that the luminaire will
be held at the fade value before turning o. A value of 0 disables the fade function.
Note: Certain parameter functions are only available in specic versions of the detectors and these are indicated under the aected parameter headings
within the brackets e.g. LUX Learn Level (V3).