infiNET EX™ Thermostat Crestron CHV-TSTATEX
Setup Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
Unacquire Gateway UA
Not started (--)
In progress
(flashing --)
Finished, success
(00)
Finished, failed (E#,
where # represents
an error code)
N/A
Used to remove gateway
information from the device, so it
will no longer communicate with the
current gateway.
”E1” indicates that there is no
previous gateway information (i.e.
the gateway may already have
been unacquired).
Communications
check
CC
Error (E# - where #
is a number from 0 to
7)
No problems (00)
N/A
Displays error codes for any
problems found, or 00 for no
problems.
Check Battery Life bA
Not started (--)
Estimated remaining
battery life (0 – 99)
N/A
Gives estimated remaining battery
life in percent.
Restore Factory
Defaults
Fd
Not started (--)
In progress (blank or
flashing --)
Finished (00)
Button not held long
enough (Er)
N/A
Restores all setup parameters to
their default settings. To prevent
accidentally performing this action,
you must press and hold either the
or button for three seconds
for this function to execute.
Perform Heat Call Test
(Toggle)
H
Not started/Heat call
off (--)
Heat call on (on)
(also, “H” icon will
turn on)
N/A
Will test the heat call output.
Bypasses short-cycle timers. Useful
for technician system testing. Note
that calling the heat may activate
other relays in the thermostat as
required, such as the fan output for
heat pump or dual-fuel types.
Perform Cool Call Test
(Toggle)
C
Not started/Cool call
off (--)
Cool call on (on)
(also, “C” icon will
turn on)
N/A
Will test the cool call output.
Bypasses short-cycle timers. Useful
for technician system testing. Note
that calling the cooling may activate
other relays in the thermostat as
required, such as the fan output.
Perform Aux Heat Call
Test (Toggle)
(will appear only on
Heat pump and Dual-
Fuel Heat pump
systems)
A
Not started/Aux call
off (--)
Aux call on (on)
(also, “A” icon will
turn on)
N/A
Same as above, for testing aux
heat output.
Perform Fan Call Test
(Toggle)
F
Not started/Fan call
off (--)
Fan call on (on)
(also, “F” icon will
turn on)
N/A
Same as above, for fan. Note that
only the fan relay can be activated
for a fan call test.
Perform Self Test St
Not started (--)
In progress
(flashing --)
Finished, self test ok
(00)
Finished, self test
failed (E#, where #
represents an error
code)
N/A
For assistance, please contact the
Crestron customer service team by
calling Crestron at
1-888-CRESTRON
(1-888-273-7876).
22 infiNET EX™ Thermostat: CHV-TSTATEX Operations & Installation Guide – DOC. 6989A

Other manuals for Crestron CHV-TSTATEX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Crestron CHV-TSTATEX and is the answer not in the manual?

Crestron CHV-TSTATEX Specifications

General IconGeneral
BrandCrestron
ModelCHV-TSTATEX
CategoryThermostat
LanguageEnglish

Related product manuals