Crestron CHV-TSTATEX infiNET EX™ Thermostat
Specifications
Specifications for the CHV-TSTATEX are listed in the following table.
CHV-TSTATEX Specifications
SPECIFICATION DETAILS
Wireless
RF Transceiver
2-way RF, 2.4 GHz ISM Channels 11-26 (2400
to 2483.6 MHz), IEEE 802.15.4 compliant
Range (typical)
150 ft (46 m) indoor, 250 ft (76 m) outdoor;
Subject to site-specific conditions; range is
increased by adding additional devices or
CLW-RFEXP-EX wireless expander (sold
separately)
Gateway
Requires a CEN-RFGW-EX RF gateway or
MC3 3-Series Control System™ (both sold
separately)
Display
Backlit LCD with two large seven-segment
digits, two small seven-segment digits, 14
dedicated symbols;
Displays ambient temperature, set point,
system mode, fan setting, call activity, low
battery, RF or control system communication
errors, firmware download progress, setup
parameter/function and value
Measurement Range
Ambient Temperature -10º to 110º F (-23º to 43º C)
Display Limits -9º to 99º F (-9º to 43º C)
Temperature Tolerance
Over Full Range ±1º F (±0.5º C)
At Room Temperatures ±1º F (+0.4/-0.2º C)
Setpoint Range
Heat only setpoint 38º to 89º F (3º to 32º C)
Cool only setpoint
59º to 99º F (15º to 37º C) or
38º to 99º F (3º to 37º C) extended cool mode
enabled
Relay Rating 1 Amp @ 40 Volts DC or 24 Volts AC (nominal)
Environmental
Temperature -10º to 110º F (-23º to 43º C)
Humidity 10% to 90% RH (non-condensing)
Power Requirements
24V
0.24 Watts (10 mA @ 24 Volts AC) supplied by
heating or cooling system
Battery
Two AA batteries, estimated one year normal
operation
(Continued on following page)