EasyManua.ls Logo

Crown Boiler PHNTM080 - Page 121

Crown Boiler PHNTM080
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
• Seizedordisconnectedboilerpump
• BlownPumpFuse
Supply Sensor – The boiler control infers the supply temperature based on the resistance measured at the supply sensor. Table
14.6ashowsthisresistanceasafunctionofwatertemperature.Becausethecontrol/supplysensorisusedastheboilerswater
temperature limit control, there are actually two “thermistors” in the supply sensor wired in parallel (Figure 10.5). The control
comparestheresistancesacrossthesetwothermistorsandpreventsboileroperationifthereisasignicantdifferencebetweenthe
readings.
Return Sensor – The boiler control infers the return temperature based on the resistance measured across a single thermistor in
the return sensor. Table 14.6a shows this resistance as a function of water temperature.
Flue Temperature Sensor–Theboilercontrolinferstheuegastemperaturebasedontheresistancemeasuredattheue
temperaturesensor.Table14.6ashowsthisresistanceasafunctionofuetemperature.Thereareactuallytwo“thermistors”in
theuetemperaturesensorwiredinparallel(Figure10.5).Thecontrolcomparestheresistancesacrossthesetwothermistorsand
preventsboileroperationifthereisasignicantdifferencebetweenthereadings.
Outdoor SensorThe boiler control infers the outdoor temperature based on the resistance measured across a single thermistor
in the outdoor sensor. Table 14.6b shows this resistance as a function of temperature.
Condensate Trap–Thecondensatetrapallowscondensatetoleavetheboilerwhilecontaininguegasses.Intheeventthat
this trap becomes blocked, condensate will start to back up in the trap. To prevent a rising condensate level from backing up
intotheheatexchanger,bothagroundwireandtheamerodwirearebondedtothistrapinsuchawaythatanabnormallyhigh
condensatelevelwillconductamecurrentdirectlytoground(Figure10.5).Theboilercontrolwillinterpretthisasalossof
ameandenterasoftlockout.SeeFigures7.35or13.3fortraplocation.
FIGURE 14.5: PRESSURE SWITCH TUBING CONNECTIONS

Other manuals for Crown Boiler PHNTM080

Related product manuals