EasyManua.ls Logo

Crown Boiler PHNTM080 - Near Boiler Piping Design

Crown Boiler PHNTM080
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
B. Near Boiler Piping Design
ProperoperationofthisboilerrequiresthatthewaterowratethroughitremainwithinthelimitsshowninTable
9.1anytimetheboilerisring.Atowratesbelowtheminimumshown,theboilersowswitchand/ortemperature
riselimitfunctionmaypreventtheboilerfromring.Flowratesthroughtheboilerinexcessofthemaximumshownin
Table 9.1 can result in excessive noise or erosion damage to piping
There are two basic methods that can be used to pipe this boiler into the system. Method #1 (primary-secondary
piping) is always preferred. Additional information on hydronic system design can be found in the I=B=R Guide RHH
published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
Table 9.1: Flow Limitations
Flow (GPM)
Model Minimum Maximum
80MBH 5.0 13.3
100MBH 5.1 13.3
120MBH 6.2 13.3
150MBH 7.7 13.3
180MBH 9.3 13.3
Method 1: Primary/Secondary Piping (Strongly Recommended)
This method can be used in heat-only applications as shown in Figure 9.2 or with an indirect water heater as shown
inFigure9.3AorFigure9.3B.Inthissystem,theowratethroughtheboiler(“secondaryloop”)iscompletely
independentoftheowratethroughthesystem(“primaryloop”).Usethefollowingguidelinestoensurethattheboiler
willhavetherequiredowshowninTable9.1regardlessoftheowintheheatingsystem.
1)SystemLoopPiping-Sizethesystemcirculatorandpipingtoobtainthedesignowratethroughtheheatingsystem
as you would on any other heating system. All piping between the expansion tank and secondary connection tees must
beatleast1”.Inordertokeeptheowratesinthesystemandboilerloopsindependentofeachother,provideatleast
8diametersofstraightpipeupstreamoftherstteeand4diametersdownstreamofthesecondtee.Keepthedistance
betweentheexpansiontankandtherstsecondaryteeasshortaspractical.
2)BoilerLoopPiping–AllboilersaresuppliedwithabuiltincirculatorwhichwilldelivertheowrequiredbyTable
9.1 provided both of the following conditions are met:
• Allpipingintheboilerloophasanominalsizeofatleast1”
• Theequivalentlengthofallpipingintheboilerloopis60ftorless.
To verify that the 60ft, equivalent length is not exceeded, do the following:
a) Countallttingsintheplannedboilerloop(theshadedpipinginFigure9.6).Indoingso,donotcountthe
secondaryconnectiontees,unions,orthettingssuppliedwiththeboiler(thesehavealreadybeenaccountedfor).
b) UsingTable9.4,ndtheequivalentlengthsofallttingsinthesecondaryloop.Totaltheseequivalentlengthsand
add them to the total length of planned straight pipe in the secondary loop.
c) The result is the total equivalent length of the planned boiler loop. If the equivalent length calculated in (b) is under
thelimitshowninTable9.5,theboilerpumpwillachieveaowrateandtemperatureriseapproximatelyequaltothat
shown in this table. Otherwise, the equivalent length must be reduced.

Other manuals for Crown Boiler PHNTM080

Related product manuals