EasyManua.ls Logo

Crown Boiler PHNTM080 - Locating the Boiler

Crown Boiler PHNTM080
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
4) Allboilersareshippedfromthefactoryconguredforusewithnaturalgas.TheymaybeconvertedforusewithLPgas
(“propane”) using a combustion analyzer in accordance with the instructions in Appendix A.
5) Not all models are suitable for installation at altitudes above 2000ft. See Appendix A for additional information.
IV Locating the Boiler
1) Observe the minimum clearances shown in Figure 4.1. These clearances apply to combustible construction as well as non-
combustiblewalls,oors,ceilingsanddoors.
2) Note the recommended service clearances in Figure 4.1. These service clearances are recommended, but may be reduced to
the combustible clearances provided:
a. Access to the front of the boiler is provided through a door.
b. Access is provided to the condensate trap located beneath the boiler.
Notethatservicingtheboilerwillbecomeincreasinglydifcultastheseserviceclearancesarereduced.
3) Observe the following clearances from piping to combustible construction:
Non-concentric vent (exhaust): ¼”
Air intake piping: 0”
Hot water piping: ¼”
4) The relief valve and gauge must be installed in the location shown in Figure 2.1 and must be in the same space as the boiler.
5) The boiler should be located so as to minimize the length of the vent system.
6) The combustion air piping must terminate where outdoor air is available for combustion and away from areas that will con-
taminatecombustionair.Avoidareasnearchemicalproductscontainingchlorine,chloridebasedsalts,chloro/uorocarbons,
paint removers, cleaning solvents and detergents.






 

 
 



Other manuals for Crown Boiler PHNTM080

Related product manuals