139
FIGURE A.1a: GAS VALVE DETAIL (80MBH THRU 120MBH)
FIGURE A.1b: GAS VALVE DETAIL (150MBH, 180MBH)
FIGURE A.1a: GAS VALVE DETAIL (80MBH THRU 120MBH)
TABLE A.2: STARTING NUMBER OF THROTTLE TURNS
FOR CONVERSION TO LP GAS
MODEL # COUNTERCLOCKWISE TURNS
(FROM FULLY CLOSED)
080 3-3/4
100 3
120 4
150 5-3/4
180 6-1/2