Cd40, 41, 42, 43
Multi-speed setting (Settable range 0.5~240)
This function has 8 kinds of speed operation
Use external terminal FR (or RR) accommodate DI1, DI2, DI3, DI4 to select different
speeds. Refer to the following table:
Cd40= 5
th
step speed setting
Cd41= 6
th
step speed setting
Cd42= 7
th
step speed setting
Cd43= 8
th
step speed setting
Example
:
DI1 set to be 2DF
、
DI2 set to be 3DF
、
DI3 set to be 5DF(DI1
~
DI4 any three
of them, could be set to be 2DF
、
3DF
、
5DF)
External Terminal ame
/Setting Function
Selective speed
2 3 4 5 6 7 8
DI1/2DF
○
○
○
○
DI2/3DF
○
○
○
○
DI3/5DF
○
○
○
○
○
: Stands for external terminal to put in.
Note: Apply to multi-speed setting external control is required for operation control
mode (e.g. Cd04=1).
§
Cd44
Stop mode (Settable range 0~2)
Cd44=0 Deceleration stop
Cd44=1 Free run stop
Cd44=2 Free run stop, but restart after the deceleration time is reached, deceleration
time is set by Cd11.
§
Cd45
Frequency detect level (Settable range 0.5~240)
This function is only available when RELAY output terminal Cd47=6 or
Cd48=6, and Cd45 is assigned.