20
Model PR750RTXL2UC PR1000RTXL2UC PR1500RTXL2UC PR2000RTXL2UC PR2200RTXL2UC PR3000RTXL2UC
General
UPS Topology Line-interactive
Energy Saving GreenPower UPS Bypass Technology
Input
Nominal Input
Voltage
100/110/120/125V 100/110/120V
Input Frequency 50/60Hz +/- 3Hz (Auto-sensing)
Plug Type NEMA 5-15P NEMA 5-20P NEMA 5-30P
Power Cord
Length
10ft / 3m
Output
Power Capacity 750VA/750W 1000VA/1000W 1500VA/1500W* 2000VA/2000W* 2200VA/2200W 3000VA/3000W*
On Battery
Output Voltage
100/110/120/125V +/- 5% 100/110/120V +/- 5%
On Battery
Output
Frequency
50/60Hz +/- 1%
On Battery
Output Waveform
Sine Wave
Battery
Battery Type Sealed Maintenance Free Lead Acid Battery
Replacement
Battery Pack
(RBP)
RB1270X4H RB1290X4J
RBP Quantity 1
Typical Recharge
Time
3 hours to 90% from total discharge under 100% load
Extended Battery
Module
BP48VP2U01 BP48VP2U02
Physical
Dimensions
2U Rack, 17.1” x 3.4” x 16.2” / 433 x 86.5
x 412 (mm)
2U Rack, 17.1” x 3.4” x 16.7” / 433 x 86.5 x 500 (mm)
Weight 53.1lbs / 24.1kg 55.3lbs / 25.1kg 67.7lbs / 30.7kg 74.5lbs / 33.8kg 79.6lbs / 36.1kg 75.4lbs / 34.2kg
Conformance
Approvals UL1778, CSA C22.2 No 107.3, FCC Class B, VCCI Class B, ENERGY STAR
UL1778, CSA C22.2 No 107.3, FCC Class
A, VCCI Class A, ENERGY STAR
Environmental RoHS Compliant
*Refer below de-rating information for 100/110V systems:
PR1500RTXL2UC: 1200VA/1200W@100V, 1350VA/1350W@110V; PR2000RTXL2UC: 1600VA/1600W@100V, 1800VA/1800W@110V; PR3000RTXL2UC:
2400VA/2400W@100V, 2700VA/2700W@110V.