Installing the CTM-ONE.
For analog voltage monitoring the measurement range is 0 to +10 volts with 10mV resolution. The input can
withstand up to 36 volts. Note that the IN GND connection is referenced to the CTM-ONE’s supply ground.
Example of single ended analog input wiring:
5.9 Auxiliary Port
Molex Micro-Fit 3.0™ connector #:
Molex Part Number
Description
43025-1000
Receptacle housing
43030
Crimp Terminals 20-24 AWG
The auxiliary connection enables communication with Maxim iButton™ Devices and provides the ability for
remote reset of the CTM-ONE when mounted in hard to access locations using a reset switch.
iButton and Reader