12 | Commissioning
Installer reference guide
61
2(A)MXM40+50 + 2(A)MXF40+50
R32 Split series
4P600463-2C – 2020.08
2 Measure the temperature at the indoor unit inlet and outlet after running the
unit for about 20minutes. The difference should be more than 8°C (cooling)
or 15°C (heating).
3 First check operation of each unit individually, then check simultaneous
operation of all indoor units. Check both heating and cooling operation.
4 When test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
INFORMATION
Test run can be disabled if necessary.
After the unit is turned OFF, it cannot be started again for 3 minutes.
During cooling operation, frost may form on the gas stop valve or other parts.
This is normal.
INFORMATION
Even if the unit is turned OFF, it consumes electricity.
When the power turns back on after a power break, the previously selected
mode will be resumed.
12.6 Starting up the outdoor unit
See the indoor unit installation manual for configuration and commissioning of the
system.

Table of Contents

Other manuals for Daikin 2MXM50M3V1B9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXM50M3V1B9 and is the answer not in the manual?

Daikin 2MXM50M3V1B9 Specifications

General IconGeneral
BrandDaikin
Model2MXM50M3V1B9
CategoryAir Conditioner
LanguageEnglish

Related product manuals