EasyManuals Logo

Daikin 4MXM-M User Manual

Daikin 4MXM-M
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
ESIE16-02B | Part 2. Troubleshooting 2.2. Error based troubleshooting
4/04/17 | Version 1.1 Page 37
RA R32 Split & multi split M-Series
More info:
Faulty outdoor unit PCB in which radiating
fin thermistor is connected.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Restore the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals.
Check procedures Replacing procedures
"Refrigerant thermistors" on page 56 "Replacing thermistors" on page 87
"Main PCB" on page 53 "Replacing main PCB" on page 84
Possible cause Check Corrective action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXM-M and is the answer not in the manual?

Daikin 4MXM-M Specifications

General IconGeneral
BrandDaikin
Model4MXM-M
CategoryAir Conditioner
LanguageEnglish

Related product manuals