EasyManua.ls Logo

Daikin 90 Plus AFUE - Page 54

Daikin 90 Plus AFUE
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
©2014DaikinNorthAmerica,LLC
CheckingDuctStatic
Thepositive staticreadingis
takenatthefurnacesupply
outlet,andmustberead
betweenthefurnaceandthe
coolingcoil.
Thenegative staticreadingis
takenatthefurnacereturnduct
inlet,andmustbereadbetween
thefurnaceandfilter.
Takeductstaticreadingsthrough
testholesinducts,andta
p
eup
holesonceyourtestiscomplete.
©2014DaikinNorthAmerica,LLC
CheckingDuctStatic
SupplyAir
Inclined
Manometer
Measure
Negative
Static
Return
Air
Stepstodeterminetotal
externalstaticpressure:
Inspect/replacefilterin
furnace.
Installaninclined
manometer,magnehelic,
ordigitalmanometerinto
returnductoffurnace
closesttoblower,but
downstreamoffilter.
Measurethenegative
staticpressureofthe
returnductattheinletof
thefurnace.