4 Set-up and installation
Installation and maintenance instructions
13
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Fig.4-4 Dimensions, top of the device - Type …04P50D/…
08P50D
Item Designation
1 Solar - inflow
2 Cold water
3 Domestic hot water
4 Heating inflow
5 Heating return flow
6 Connection for refrigerant gas line
7 Connection for refrigerant fluid line
8 Biv – inflow (…Biv type only)
9 Biv – return flow (…Biv type only)
A front
B rear
Tab.4-1
4.2 Transport and delivery
WARNING
When unfilled, the indoor unit is top-heavy and could tip
over during transport. That could put persons in danger or
damage the unit.
▪ Secure the indoor unit well, transport carefully, use the
handles.
The indoor unit is delivered on a pallet. All industrial trucks, such as
lifting trucks and forklift trucks, are suitable for transporting it.
Scope of delivery
▪ Indoor unit (pre-mounted),
▪ Bag of accessories (see Fig. 4-5),
▪ Document pack.
Fig.4-5 Contents of bag of accessories
Item Designation Item Designation
A Handles (only required
for transport)
G O-ring
B cover panel H Cable tie
C Hose connecting piece
for safety overflow
I Plug bracket
D Assembly wrench J Venting hose
E Ball valve K Drain hose cover
F Flat gasket L Controller rotary switch
Tab.4-2
For further accessories for the indoor unit, see price list.
4.3 Installing the heat pump
4.3.1 Selecting the installation site
CAUTION
If the total refrigerant charge in the system is ≥ 1.84kg, it is
essential to comply with additional requirements for min-
imum footprint and minimum ventilation openings.
ObserveChap. 10.5.
Information on the total refrigerant charge can be found on
the type plate of the outdoor unit. Please follow the installa-
tion instructions.
The installation site of the indoor unit must meet the minimum re-
quirements below (see alsoChap. 1.2.3).