8 Faults and malfunctions
Installation and maintenance instructions
41
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Malfunction Possible cause Possible solution
Heating does not warm
up enough
Water flow too low.
Check that all stop valves of the water circuit are fully open.
Check that the water filter is dirty.
Check if the expansion tank is defective.
Completely vent the heating system and the internal circula-
tion pump.
On the controller ("Information" menu), check that sufficient
water pressure (>0.5bar) is available; if necessary, top up
heating water.
Check that the resistance in the water circuit is not too high
for the pump (see Chap. 10).
Target value range is too low. In [→Main menu →Configuration →Heating]:
Increase the [Heat-Slope ] parameter.
Increase the [HZU max. temperature ] parameter.
Increase the [Max. feed temperature] parameter.
Weather-compensated inflow temperature control
active.
Check the [Heating operation limit] parameter, [Heat-Slope] in
[→Main menu →Configuration →Heating].
Optional backup heater (EKBUxx) or alternative
heater booster not cut in.
Check mains supply of the backup heater (EKBUxx).
Thermal contactor (STB) on the backup heater (EKBUxx) has
triggered. Unlock.
Check the [Config. of external heat source] and [Ext. power
level 1] and [Ext. power level 2] parameters [→Main menu
→Settings →Ext. source].
Water volume in heating system too low
Check the admission pressure in the expansion tank and wa-
ter pressure; if necessary, top up the heating water and adjust
the admission pressure (seeChap. 7.2.2).
Domestic hot water preparation is taking too much of
the output of the heat pump.
Check the settings of the [Config. of external heat source]
parameter [→Main menu →Settings →Ext. source].
Check the settings of the [Ext. hot water power] parameter
[→Main menu →Settings →Ext. source].
Hot water does not
warm up
Domestic hot water preparation shut off (e.g. switch-
ing time program is in the economy phase, paramet-
ers for domestic hot water preparation incorrectly
set).
Check the operating mode setting.
Check the request parameters.
Storage tank charging temperature too low.
Increase the target hot water temperature.
Draw-off rate too high.
Reduce the draw-off rate, limit throughput.
Output of heat pump too low.
Check the switching times for room heating and domestic hot
water preparation for overlaps.
Water volume in heating system too low.
Check the admission pressure in the expansion tank and wa-
ter pressure; if necessary, top up the heating water and adjust
the admission pressure.
Optional backup heater (EKBUxx) or alternative
heater booster not cut in.
Check mains supply of the backup heater (EKBUxx).
Thermal contactor (STB) on the backup heater (EKBUxx) has
triggered. Unlock.
Check the [Config. of external heat source] and [Ext. power
level 1] and [Ext. power level 2] parameters [→Main menu
→Settings →Ext. source].