8 Faults and malfunctions
Installation and maintenance instructions
50
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Code Component/Designation Error Possible fault rectification
E9046 Software Compressor start-up System detects an abnormal electricity wave shape
16 times in 5min
Check that the power supply meets the regula-
tions. Check for frequency fluctuations.
Check the compressor.
Check the compressor's connection and wiring.
Check the operation of the expansion valve (fluid
return flow).
Check the refrigerant filling capacity and check for
leaks.
After resetting the power supply, check if the error
occurs when the compressor is not in operation:
check the expansion valve.
E9047 Software Overvoltage System detects an overcurrent of >20A to the com-
pressor for >2.5seconds 16x in 5min
Check the compressor.
Check the compressor's connection and wiring.
Check the operation of the expansion valve (fluid
return flow).
Check the refrigerant filling capacity and check for
leaks.
Check the power transistor.
Check the outer inverter conductor plate.
Check that the current flow LED flashes at regular
intervals.
Check that the correct replacement part has been
installed.
Check that the outer main conductor plate is re-
ceiving a power supply.
Check that the power supply meets the regula-
tions. Check for frequency fluctuations.
E9048 4-way valve 4-way valve The following condition occurs for 10min after oper-
ation for 5min:
Heating: Temperature of the condenser negative
outlet water temperature <-10°C
Check the thermistor for the outlet water in the
heat exchanger.
Check the thermistor for the refrigerant fluid side.
Check that the current flow LED flashes at regular
intervals.
Check that the correct replacement part has been
installed.
Check that the outer main conductor plate is re-
ceiving a power supply.
Check the 4-way valve coil/wiring harness.
Check the 4-way valve body.
Check for insufficient refrigerant. Perform a leak
test.
Check the quality of the refrigerant.
Check the shut-off valves.
Check that the hydro printed circuit board is being
supplied with voltage.