9 | Electrical installation
Installer reference guide
107
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
L N PE
b
a
L
N
Q1DI
1N~,
50 Hz,
230 V AC
F1B
1
3
2
4
II
BRN
BLU
YLW/GRN
b
a
L
N
a Power supply cable (field supply)
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2 pole, 32A fuse, C curve.
Q1DI Earth leakage circuit breaker (30mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
Route the cable through the frame.
Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
Fix the cable with a cable tie.
Wires: (3+GND)×1.5mm²