4P644482-1 – 2021.03
6.5.4 Preferential kWh rate power supply
General rule
▪ Power meter1: Measures the outdoor unit.
▪ Power meter2: Measures the rest (i.e. indoor unit and backup heater).
Setup
▪ Connect power meter1 to X5M/5 and X5M/6.
▪ Connect power meter2 to X5M/3 and X5M/4.
See "9.3.4To connect the electricity meters"[4122].
Power meter types
▪ Power meter 1: Single- or three-phase power meter according to the power
supply of the outdoor unit.
▪ Power meter2:
- In case of a single-phase backup heater configuration, use a single-phase
power meter.
- In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
e fe
ihg
A B
b
a
d
c
5
8
0
1
5
0
0
0
5
8
0
1
5
0
0
0
A Outdoor unit
B Indoor unit
a Electrical cabinet (L
1
/N): Preferential kWh rate power supply
b Electrical cabinet (L
1
/L
2
/L
3
/N): Normal kWh rate power supply
c Power meter (L
1
/N)
d Power meter (L
1
/L
2
/L
3
/N)
e Fuse (L
1
/N)
f Fuse (L
1
/L
2
/L
3
/N)
g Outdoor unit (L
1
/N)
h Indoor unit (L
1
/N)
i Backup heater (L
1
/L
2
/L
3
/N)
6.6 Setting up the power consumption control
You can use the following power consumption controls. For more information
about the corresponding settings, see "Power consumption control"[4208].