16 | Technical data
Installer reference guide
281
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
16.7 ESP curve: Indoor unit
Note: A flow error will occur when the minimum water flow rate is not reached.
FED
0 5
70
60
80
50
40
30
20
10
0
10 15 20 25 30 35 40 45
A (kPa)
B (l/min)
C
A External static pressure in the space heating/cooling circuit
B Water flow rate through the unit in the space heating/cooling circuit
C Operation range
D Minimum flow during normal operation
E Minimum flow during backup heater operation
F Minimum flow during defrost heater operation
Dashed lines: Operation area is extended to lower flow rates only in case the unit
operates with heat pump only. (Not in startup, no backup heater operation, no
defrost operation.)
Notes:
Selecting a flow outside the operating area can damage the unit or cause the unit
to malfunction. See also the minimum and maximum allowed water flow range in
the technical specifications.
Make sure water quality complies with EU directive 2020/2184.