9 | Electrical installation
Installer reference guide
119
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Backup heater
type
Backup
heater
capacity
Power supply Maximum
running current
Z
max
*6V 2kW 1N~230V
(a)
9A —
4kW 1N~230V
(a)
17A
(b)(c)
0.22Ω
6kW 1N~230V
(a)
26A
(b)(c)
0.22Ω
2kW 3~230V
(d)
5A —
4kW 3~230V
(d)
10A —
6kW 3~230V
(d)
15A —
*9W 3kW 3N~400V 4A —
6kW 3N~400V 9A —
9kW 3N~400V 13A —
(a)
6V3
(b)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16A and ≤75A per phase).
(c)
This equipment complies with EN/IEC61000‑3‑11 (European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems for equipment with rated current ≤75A) provided that the
system impedance Z
sys
is less than or equal to Z
max
at the interface point between the user's
supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system impedance Z
sys
less than or
equal to Z
max
.
(d)
6T1
Connect the backup heater power supply as follows:
a Factory-mounted cable connected to the contactor of the backup heater, inside the
switch box (K5M)
b Field wiring (see table below)