3 | Specific installer safety instructions
Installer reference guide
17
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Mounting the indoor unit (see
"7.4Mounting the indoor unit"[
4
80]
)
WARNING
Fixing method of the indoor unit MUST be in accordance with the instructions from
this manual. See "7.4Mounting the indoor unit"[480].
Opening and closing the units (see
"7.2Opening and closing the units"[
4
68]
)
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Piping installation (see
"8Piping installation"[
4
82]
)
WARNING
Field piping method MUST be in accordance with the instructions from this manual.
See "8Piping installation"[482].
WARNING
The discharge pipes from the pressure relief valves MUST terminate in a safe and
visible position without forming any risk to persons in the vicinity.
WARNING
Discharge piping, tundish, drain valves, etc. MUST be positioned away from any
electrical components.
The discharge pipe away from the tundish MUST terminate in a safe, visible
position without forming any risk to persons in the vicinity.
WARNING
Do NOT install any valves between the domestic hot water tank and relief valves/
expansion vessel.
Do NOT install shut-off valves between the expansion relief valve and the
domestic hot water tank.
WARNING
Install the tundish away from any electrical device. Possible consequence: Electrical
shock or fire.
In case of freeze protection by glycol: