10 | Configuration
Installer reference guide
181
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Value Description
0 No limitation
1~4 General limitation. There is limitation in all conditions. The
required delta T control and comfort are NOT guaranteed.
▪ 1: 90% pump speed
▪ 2: 80% pump speed
▪ 3: 70% pump speed
▪ 4: 60% pump speed
5~8 Limitation when no actuators. When there is no heating output,
the pump speed limitation is applicable. When there is heating
output, the pump speed is only determined by deltaT in
relation to the required capacity. With this limitation range,
deltaT is possible and the comfort is guaranteed.
During sampling operation the pump runs for a short time to
measure the water temperatures, which indicate if operation is
required or not.
▪ 5: 90% pump speed during sampling
▪ 6: 80% pump speed during sampling
▪ 7: 70% pump speed during sampling
▪ 8: 60% pump speed during sampling
The maximum values depend on the unit type:
[9-0D]/[9-0E]=0 [9-0D]/[9-0E]=1/5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]/[9-0E]=2/6 [9-0D]/[9-0E]=3/7