10 | Configuration
Installer reference guide
219
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Bizone kit system type
# Code Description
[9.P.2] [E-0C] Bizone system type
▪ 0 Without hydraulic separator / no
direct pump
▪ 1 With hydraulic separator / no
direct pump
▪ 2 With hydraulic separator / with
direct pump
a:Indoor unit; b:Mixing station; c:Hydraulic
separator; d:Direct pump
Additional zone pump fixed PWM
The speed of the additional zone pump can be fixed with this setting.
# Code Description
[9.P.3] [7-0A] Add zone pump fixed PWM: Fixed pump
speed for additional (direct) zone.
▪ 20~95% (default: 95)
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
# Code Description
[9.P.4] [7-0B] Main zone pump fixed PWM: Fixed pump
speed for main (mixed) zone.
▪ 20~95% (default: 95)