3/13
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
2.D.1 [F-0B] R/W
0: No
1: Yes
2.D.2 [F-0C] R/W 0: No
1: Yes
Main zone
2.E R/W 0: 2-points
1: Slo
e-Offset
Additional zone
3.4 0: Fixed
1: WD heating, fixed cooling
2: Weather de
endent
└─ Heating WD curve
3.5 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
3.5 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
65°C
3.5 [0-02] R/W 10~25°C, step: 1°C
15°C
3.5 [0-03] R/W -40~5°C, step: 1°C
-15°C
└─ Cooling WD curve
3.6 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
7°C
[2-0C]=2:
18°C
3.6 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C
3.6 [0-06] R/W 25~43°C, step: 1°C
35°C
3.6 [0-07] R/W 10~25°C, step: 1°C
20°C
Additional zone
3.7 [2-0D] R/O 0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1 [9-05] R/W 15~37°C, step: 1°C
25°C
3.8.2 [9-06] R/W [2-0C]=2:
37~65, step: 1°C
65°C
[2-0C]≠2:
37~55, step: 1°C
55°C
3.8.3 [9-07] R/W 5~18°C, step: 1°C
7°C
3.8.4 [9-08] R/W 18~22°C, step: 1°C
22°C
Additional zone
3.A [C-06] R/W 0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1 [1-0C] [2-0D] ≠2
R/W
[2-0D] =2
R/O
[2-0D]≠2
(Radiator):
3~10°C, step: 1°C
5°C
[2-0D]=2
(Radiator):
10°C
3.B.2 [1-0E] R/W 3~10°C, step: 1°C
5°C
Additional zone
3.C R/O 0: 2-points
1: Slo
e-Offset
Space heating / cooling
└─ Operation range
4.3.1 [4-02] R/W 14~35°C, step: 1°C
35°C
4.3.2 [F-01] R/W 10~35°C, step: 1°C
20°C
Space heating / cooling
4.4 [7-02] R/W
0: 1 LWT zone
1: 2 LWT zones
4.5 [F-0D] R/W 0: Continuous
1: Sample
2: Re
uest
4.6 [E-02] R/W (*5)
R/O (*6)
0: Reversible (*5)
1: Heating only (*6)
4.7 [9-0D] R/W 0~8, step: 1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6: 80% pump speed durin
Space heating / cooling
4.9 [F-00] R/W
0: Restricted
1: Allowed
4.A [D-03] R/W 0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, s
an 8°C
4.B [9-04] R/W 1~4°C, step: 1°C
1°C
During thermo
During cooling
WD curve type
Setpoint mode
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
Thermostat type
Delta T heating
Delta T cooling
WD curve type
Space heating OFF temp
Space cooling OFF temp
Number of zones
Pump operation mode
Unit type
Pump speed limitation
Pump outside range
Increase around 0°C
Overshoot
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_
(*7) *18*_(*8) *23*
4P634891-1 - 2021.03